Back to the backflow review queue

Backflow assembly test: 4739 Mill Creek Ct

Approved

Filed Jul 18, 2024 by Emerson Stroud, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 18, 2024
Assembly type
PVB
Serial number
A313902
Size
1
Test gauge serial
G-6643
Gauge calibration date
Apr 9, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Stroud, current on the service date
  • All required fields present
  • Address matches parcel 067-15-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4739 Mill Creek Ct
Owner: Drew Pruitt
Parcel 067-15-01121