Backflow assembly test: 9012 Mill Creek Way
ApprovedFiled May 31, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 31, 2024
- Assembly type
- DC
- Serial number
- A697913
- Size
- 1
- Test gauge serial
- G-2118
- Gauge calibration date
- Mar 13, 2024
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-97-01184
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.