Back to the backflow review queue
Backflow assembly test: 2298 Cedar Hollow Ct
ApprovedFiled Jul 29, 2025 by Avery Benton, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 29, 2025
- Assembly type
- DC
- Serial number
- Z772095
- Size
- 3/4
- Test gauge serial
- G-5097
- Gauge calibration date
- Feb 3, 2025
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Benton, current on the service date
- All required fields present
- Address matches parcel 067-50-01083
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2298 Cedar Hollow Ct
Owner: Parker Nguyen
Parcel 067-50-01083