Back to the backflow review queue

Backflow assembly test: Blue Heron Grill

Approved

Filed Mar 19, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 19, 2025
Assembly type
DC
Serial number
B900469
Size
1 1/2
Test gauge serial
G-5654
Gauge calibration date
May 25, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-54-01310
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1797 Stone Gate Dr
Owner: Harlow Holdings LLC
Parcel 067-54-01310