Backflow assembly test: 7694 Pine Knoll Trl
ApprovedFiled Oct 2, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 2, 2026
- Assembly type
- RP
- Serial number
- Z443364
- Size
- 1
- Test gauge serial
- G-9844
- Gauge calibration date
- Jan 25, 2026
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 067-49-01195
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.