Backflow assembly test: 5339 Mill Creek Dr
ApprovedFiled Jan 30, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 30, 2024
- Assembly type
- RP
- Serial number
- B634172
- Size
- 1
- Test gauge serial
- G-8796
- Gauge calibration date
- Sep 29, 2023
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-59-01292
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.