Backflow assembly test: 1839 Sycamore Dr

Approved

Filed May 18, 2026 by Reese Danner, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 18, 2026
Assembly type
RP
Serial number
W209360
Size
1
Test gauge serial
G-6310
Gauge calibration date
Feb 6, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-26-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.