Backflow assembly test: 1854 Laurel Trl

Approved

Filed Sep 26, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 26, 2024
Assembly type
RP
Serial number
K204758
Size
1
Test gauge serial
G-8955
Gauge calibration date
Mar 13, 2024
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
1.8 psid
Relief valve opened at
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-43-01027
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1854 Laurel Trl
Owner: Emerson Whitcomb
Parcel 067-43-01027