Backflow assembly test: 3919 Spring Branch Ln
ApprovedFiled Apr 20, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 20, 2025
- Assembly type
- DC
- Serial number
- B323872
- Size
- 3/4
- Test gauge serial
- G-8076
- Gauge calibration date
- Nov 27, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-92-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.