Backflow assembly test: 3139 Quarry Dr

Approved

Filed Dec 10, 2024 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 10, 2024
Assembly type
RP
Serial number
B392607
Size
3/4
Test gauge serial
G-3240
Gauge calibration date
Feb 19, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Stroud, current on the service date
  • All required fields present
  • Address matches parcel 067-76-01065
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.