Backflow assembly test: 342 Stone Gate Rd
ApprovedFiled Jun 30, 2026 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 30, 2026
- Assembly type
- PVB
- Serial number
- K261766
- Size
- 3/4
- Test gauge serial
- G-8422
- Gauge calibration date
- Apr 4, 2026
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-53-01031
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
342 Stone Gate Rd
Owner: Taylor Vance
Parcel 067-53-01031