Backflow assembly test: 4667 Quarry Way

Approved

Filed Jul 7, 2025 by Emerson Stroud, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 7, 2025
Assembly type
RP
Serial number
K809722
Size
3/4
Test gauge serial
G-7180
Gauge calibration date
Feb 3, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Stroud, current on the service date
  • All required fields present
  • Address matches parcel 067-55-01088
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4667 Quarry Way
Owner: Morgan Marsh
Parcel 067-55-01088