Backflow assembly test: 566 Fox Run Way
ApprovedFiled Sep 11, 2026 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 11, 2026
- Assembly type
- PVB
- Serial number
- B823966
- Size
- 3/4
- Test gauge serial
- G-1584
- Gauge calibration date
- May 14, 2026
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-68-01095
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.