Backflow assembly test: 7922 Laurel Ct

Approved

Filed Feb 26, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 26, 2026
Assembly type
RP
Serial number
K706785
Size
3/4
Test gauge serial
G-5808
Gauge calibration date
Jan 5, 2026
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-46-01291
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7922 Laurel Ct
Owner: Parker Nguyen
Parcel 067-46-01291