Back to the backflow review queue

Backflow assembly test: 8570 Meadow Lark Dr

Approved

Filed Nov 7, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 7, 2026
Assembly type
RP
Serial number
W114417
Size
1
Test gauge serial
G-4150
Gauge calibration date
Jul 19, 2026
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-91-01199
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8570 Meadow Lark Dr
Owner: Parker Harlow
Parcel 067-91-01199