Backflow assembly test: 2053 Orchard Ln
ApprovedFiled Jan 20, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 20, 2026
- Assembly type
- PVB
- Serial number
- W522027
- Size
- 3/4
- Test gauge serial
- G-9353
- Gauge calibration date
- Nov 3, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-65-01096
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2053 Orchard Ln
Owner: Quinn Hollins
Parcel 067-65-01096