Back to the backflow review queue

Backflow assembly test: Station Medical Offices

Approved

Filed Oct 16, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 16, 2026
Assembly type
RP
Serial number
B376140
Size
1
Test gauge serial
G-8829
Gauge calibration date
Aug 1, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-64-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1662 Spring Branch Trl
Owner: Benton Holdings LLC
Parcel 067-64-01147