Back to the backflow review queue
Backflow assembly test: 9213 Mill Creek Ct
ApprovedFiled Jun 6, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 6, 2025
- Assembly type
- DC
- Serial number
- B229620
- Size
- 3/4
- Test gauge serial
- G-9352
- Gauge calibration date
- Feb 21, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 065-74-01198
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9213 Mill Creek Ct
Owner: Cameron Kessler
Parcel 065-74-01198