Back to the backflow review queue

Backflow assembly test: 3431 Laurel Ct

Approved

Filed Aug 1, 2025 by Reese Calloway, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Aug 1, 2025
Assembly type
RP
Serial number
B870467
Size
3/4
Test gauge serial
G-2430
Gauge calibration date
Apr 27, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 065-58-01350
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3431 Laurel Ct
Owner: Logan Benton
Parcel 065-58-01350