Backflow assembly test: Maple Leaf Car Wash
ApprovedFiled Sep 7, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 7, 2025
- Assembly type
- RP
- Serial number
- W467650
- Size
- 2
- Test gauge serial
- G-5323
- Gauge calibration date
- Apr 5, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 065-38-01166
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.