Backflow assembly test: 7920 Laurel Dr

Approved

Filed Jul 4, 2026 by Reese Whitcomb, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 4, 2026
Assembly type
RP
Serial number
K811205
Size
1
Test gauge serial
G-1804
Gauge calibration date
Feb 3, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 065-20-01206
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7920 Laurel Dr
Owner: Reese Calloway
Parcel 065-20-01206