Back to the backflow review queue

Backflow assembly test: Hilltop Apartments

Approved

Filed Jun 9, 2026 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 9, 2026
Assembly type
RP
Serial number
Z354870
Size
2
Test gauge serial
G-4427
Gauge calibration date
Oct 24, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 065-67-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4163 Sycamore Ct
Owner: Wexler Holdings LLC
Parcel 065-67-01340