Back to the backflow review queue

Backflow assembly test: Hilltop Dental

Approved

Filed May 20, 2025 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 20, 2025
Assembly type
RP
Serial number
A209659
Size
4
Test gauge serial
G-5340
Gauge calibration date
Aug 29, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 065-12-01178
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3468 Orchard Ln
Owner: Harlow Holdings LLC
Parcel 065-12-01178