Backflow assembly test: 2487 Pine Knoll Ct

Approved

Filed Sep 21, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 21, 2025
Assembly type
PVB
Serial number
A152752
Size
3/4
Test gauge serial
G-7254
Gauge calibration date
May 10, 2025
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 065-82-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2487 Pine Knoll Ct
Owner: Riley Ashby
Parcel 065-82-01327