Backflow assembly test: 6154 Pine Knoll Trl
ApprovedFiled Sep 18, 2026 by Blake Harlow, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 18, 2026
- Assembly type
- PVB
- Serial number
- W647792
- Size
- 3/4
- Test gauge serial
- G-6152
- Gauge calibration date
- Aug 11, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Harlow, current on the service date
- All required fields present
- Address matches parcel 065-40-01121
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6154 Pine Knoll Trl
Owner: Logan Whitcomb
Parcel 065-40-01121