Backflow assembly test: Hilltop Diner
ApprovedFiled Aug 16, 2026 by Morgan Wexler, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 16, 2026
- Assembly type
- RP
- Serial number
- B843546
- Size
- 2
- Test gauge serial
- G-4928
- Gauge calibration date
- Jan 27, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Wexler, current on the service date
- All required fields present
- Address matches parcel 065-22-01294
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.