Back to the backflow review queue
Backflow assembly test: 2305 Ridgeview Ln
ApprovedFiled Dec 16, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 16, 2025
- Assembly type
- PVB
- Serial number
- B699772
- Size
- 3/4
- Test gauge serial
- G-9894
- Gauge calibration date
- Apr 30, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 065-27-01303
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2305 Ridgeview Ln
Owner: Alex Wexler
Parcel 065-27-01303