Backflow assembly test: 8037 Meadow Lark Ln
ApprovedFiled Oct 29, 2024 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 29, 2024
- Assembly type
- DC
- Serial number
- Z847149
- Size
- 1
- Test gauge serial
- G-5179
- Gauge calibration date
- Oct 9, 2023
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 065-84-01292
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.