Back to the backflow review queue

Backflow assembly test: 4224 Sycamore Ct

Approved

Filed May 28, 2024 by Reese Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 28, 2024
Assembly type
DC
Serial number
B548116
Size
1
Test gauge serial
G-5862
Gauge calibration date
Jun 24, 2023
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 065-78-01014
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4224 Sycamore Ct
Owner: Morgan Calloway
Parcel 065-78-01014