Back to the backflow review queue

Backflow assembly test: 7313 Fox Run Dr

Approved

Filed Aug 20, 2026 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 20, 2026
Assembly type
RP
Serial number
A167394
Size
3/4
Test gauge serial
G-1984
Gauge calibration date
Jul 9, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 065-48-01266
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7313 Fox Run Dr
Owner: Sam Ashby
Parcel 065-48-01266