Back to the backflow review queue

Backflow assembly test: 466 Pine Knoll Way

Approved

Filed Jan 26, 2025 by Blake Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 26, 2025
Assembly type
RP
Serial number
Z388088
Size
3/4
Test gauge serial
G-8647
Gauge calibration date
Apr 23, 2024
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Brandt, current on the service date
  • All required fields present
  • Address matches parcel 065-33-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

466 Pine Knoll Way
Owner: Hayden Whitcomb
Parcel 065-33-01308