Backflow assembly test: 1681 Meadow Lark Rd
ApprovedFiled Mar 8, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 8, 2025
- Assembly type
- DC
- Serial number
- Z781740
- Size
- 3/4
- Test gauge serial
- G-1028
- Gauge calibration date
- Dec 12, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 065-22-01136
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.