Backflow assembly test: 3093 Laurel Dr
ApprovedFiled Sep 21, 2026 by Blake Harlow, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 21, 2026
- Assembly type
- RP
- Serial number
- B539344
- Size
- 3/4
- Test gauge serial
- G-7351
- Gauge calibration date
- Dec 2, 2025
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Harlow, current on the service date
- All required fields present
- Address matches parcel 065-39-01317
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.