Back to the backflow review queue

Backflow assembly test: 1309 Turkey Hill Ln

Approved

Filed May 11, 2026 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 11, 2026
Assembly type
RP
Serial number
W529762
Size
3/4
Test gauge serial
G-3583
Gauge calibration date
Jul 18, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 065-88-01263
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1309 Turkey Hill Ln
Owner: Quinn Stroud
Parcel 065-88-01263