Back to the backflow review queue

Backflow assembly test: 3585 Turkey Hill Dr

Approved

Filed Jul 28, 2025 by Jamie Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 28, 2025
Assembly type
RP
Serial number
A865220
Size
1
Test gauge serial
G-5671
Gauge calibration date
Feb 21, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Kessler, current on the service date
  • All required fields present
  • Address matches parcel 061-20-01072
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3585 Turkey Hill Dr
Owner: Alex Stroud
Parcel 061-20-01072