Back to the backflow review queue
Backflow assembly test: 3585 Turkey Hill Dr
ApprovedFiled Aug 13, 2024 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 13, 2024
- Assembly type
- RP
- Serial number
- A865220
- Size
- 1
- Test gauge serial
- G-7860
- Gauge calibration date
- Feb 27, 2024
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Calloway, current on the service date
- All required fields present
- Address matches parcel 061-20-01072
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.