Backflow assembly test: Hilltop Dental

Approved

Filed Aug 3, 2025 by Alex Benton, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 3, 2025
Assembly type
RP
Serial number
B302205
Size
2
Test gauge serial
G-5741
Gauge calibration date
Mar 21, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 061-67-01175
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8086 Spring Branch Rd
Owner: Pruitt Holdings LLC
Parcel 061-67-01175