Back to the backflow review queue
Backflow assembly test: 773 Spring Branch Ct
ApprovedFiled Sep 16, 2023 by Alex Benton, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 16, 2023
- Assembly type
- PVB
- Serial number
- A634586
- Size
- 3/4
- Test gauge serial
- G-5540
- Gauge calibration date
- Jun 12, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 061-97-01134
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
773 Spring Branch Ct
Owner: Riley Marsh
Parcel 061-97-01134