Backflow assembly test: 8086 Sycamore Ln
ApprovedFiled Oct 23, 2025 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 23, 2025
- Assembly type
- PVB
- Serial number
- K564806
- Size
- 1
- Test gauge serial
- G-2196
- Gauge calibration date
- Apr 10, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Calloway, current on the service date
- All required fields present
- Address matches parcel 061-60-01261
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.