Back to the backflow review queue
Backflow assembly test: 2307 Spring Branch Dr
ApprovedFiled May 11, 2026 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 11, 2026
- Assembly type
- RP
- Serial number
- K621573
- Size
- 3/4
- Test gauge serial
- G-6288
- Gauge calibration date
- May 25, 2025
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 061-54-01338
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2307 Spring Branch Dr
Owner: Morgan Ashby
Parcel 061-54-01338