Back to the backflow review queue

Backflow assembly test: Blue Heron Elementary School

Approved

Filed Apr 9, 2025 by Casey Pruitt, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 9, 2025
Assembly type
DC
Serial number
B816040
Size
1 1/2
Test gauge serial
G-3622
Gauge calibration date
Oct 24, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 061-87-01307
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8520 Ridgeview Ct
Owner: Harlow Holdings LLC
Parcel 061-87-01307