Back to the backflow review queue
Backflow assembly test: 5776 Hickory Ln
Needs reviewFiled Nov 23, 2026 by Casey Pruitt, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- RP
- Serial number
- K835244
- Size
- 3/4
- Test gauge serial
- G-4286
- Gauge calibration date
- Feb 22, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Pruitt, current on the service date
- All required fields present
- Address matches parcel 061-19-01037
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
5776 Hickory Ln
Owner: Morgan Vance
Parcel 061-19-01037