Back to the backflow review queue

Backflow assembly test: Riverside Apartments

Approved

Filed Aug 26, 2025 by Jamie Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 26, 2025
Assembly type
RP
Serial number
Z129874
Size
4
Test gauge serial
G-3321
Gauge calibration date
Apr 3, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Kessler, current on the service date
  • All required fields present
  • Address matches parcel 061-92-01277
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

746 Sycamore Trl
Owner: Calloway Holdings LLC
Parcel 061-92-01277