Back to the backflow review queue

Backflow assembly test: Maple Leaf Grill

Approved

Filed May 20, 2025 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 20, 2025
Assembly type
RP
Serial number
A324930
Size
1 1/2
Test gauge serial
G-1134
Gauge calibration date
Dec 21, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Calloway, current on the service date
  • All required fields present
  • Address matches parcel 061-39-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1505 Pine Knoll Dr
Owner: Danner Holdings LLC
Parcel 061-39-01051