Backflow assembly test: Maple Leaf Grill
ApprovedFiled May 20, 2025 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 20, 2025
- Assembly type
- RP
- Serial number
- A324930
- Size
- 1 1/2
- Test gauge serial
- G-1134
- Gauge calibration date
- Dec 21, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Calloway, current on the service date
- All required fields present
- Address matches parcel 061-39-01051
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1505 Pine Knoll Dr
Owner: Danner Holdings LLC
Parcel 061-39-01051