ApprovedFiled Feb 12, 2025 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 12, 2025
- Assembly type
- RP
- Serial number
- B202135
- Size
- 3/4
- Test gauge serial
- G-2360
- Gauge calibration date
- Jul 16, 2024
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 061-69-01236
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.