Back to the backflow review queue

Backflow assembly test: 5933 Orchard Way

Approved

Filed Jan 4, 2025 by Logan Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 4, 2025
Assembly type
RP
Serial number
B451988
Size
3/4
Test gauge serial
G-2388
Gauge calibration date
Aug 9, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 059-45-01008
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5933 Orchard Way
Owner: Morgan Fairley
Parcel 059-45-01008