Back to the backflow review queue
Backflow assembly test: Main Street Self Storage
Needs reviewFiled Nov 22, 2026 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 22, 2026
- Assembly type
- DC
- Serial number
- A778655
- Size
- 1
- Test gauge serial
- G-4196
- Gauge calibration date
- Apr 26, 2026
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Stroud, current on the service date
- All required fields present
- Address matches parcel 059-42-01164
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
9838 Hickory Rd
Owner: Calloway Holdings LLC
Parcel 059-42-01164