Back to the backflow review queue

Backflow assembly test: Corner Pizza

Approved

Filed Jan 12, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 12, 2026
Assembly type
RP
Serial number
Z728941
Size
1
Test gauge serial
G-1214
Gauge calibration date
Nov 14, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-12-01107
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5638 Ridgeview Ln
Owner: Nguyen Holdings LLC
Parcel 059-12-01107