Back to the backflow review queue

Backflow assembly test: 2004 Old Church Trl

Approved

Filed Nov 3, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 3, 2026
Assembly type
RP
Serial number
W192701
Size
3/4
Test gauge serial
G-7865
Gauge calibration date
Jul 17, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-98-01098
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2004 Old Church Trl
Owner: Jordan Marsh
Parcel 059-98-01098