Backflow assembly test: 5622 Sycamore Rd
ApprovedFiled Apr 2, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 2, 2026
- Assembly type
- RP
- Serial number
- K222662
- Size
- 3/4
- Test gauge serial
- G-1514
- Gauge calibration date
- Jan 15, 2026
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-22-01356
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.